20:10:39:56Analysis

Section · Administrative Rules of South Dakota · View on sdlegislature.gov ↗

Rulemaking activity

of the data collected during the tests. The qualified testing analyst examines the data recorded for the 48 hour test and shall determine the highest steady-state value of cow contact voltage or cow contact current. The qualified testing analyst shall determine the value of primary neutral to reference voltage that was present for the highest cow contact value. These values are identified as cow contact voltage or cow contact current and primary neutral to reference voltage at the time of maximum cow contact voltage or cow contact current. These values are recorded as Vcc48 hr, Icc48 hr, or Vp48 hr. The three data sets created from the values are: (1) The primary to reference ground voltage and the cow contact voltage or cow contact current measured during the load box test with the farm power off and the load box off shall be recorded as Vp OFF and either Vcc OFF or Icc OFF; (2) The primary to reference ground voltage and the cow contact voltage or cow contact current measured with the load box set at one-half load shall be recorded as Vp HALF LOAD and either Vcc HALF LOAD or Icc HALF LOAD;and (3) The primary to reference ground voltage and the cow contact voltage or cow contact current measured with the load box at maximum shall be recorded as Vp FULL LOAD and either Vcc FULL LOAD or Icc FULL LOAD.

Source: 42 SDR 174, effective June 21, 2016.