of any contributions to stray current or voltage for single phase dairies. The utility contribution to cow contact voltage or cow contact current is determined by the following formulas: (1) Utility contribution to cow contact voltage = ((Vp48 - VP Half) / (Vp Full - Vp Half)) x (Vcc Full - Vcc Half) + Vcc HALF; or (2) Utility contribution to cow contact current = ((Vp48 - Vp HALF) / (Vp FULL - Vp HALF)) x (Icc FULL - Icc Half) + Icc HALF. The values determined are compared to the preventive action level.

Source: 42 SDR 174, effective June 21, 2016.