44:73:12:26Steam and hot water systems.

Section · Administrative Rules of South Dakota · View on sdlegislature.gov ↗

Boilers must have the capacity to supply the normal requirements of all of the facility's systems and equipment. Supply and return mains and risers of space heating and process steam systems must be valved to isolate the various sections of each system. Each piece of equipment must be valved at the supply and return end. Boilers, smoke breeching, steam supply piping, high pressure steam return piping, and hot water space heating supply and return piping must be insulated with insulation having a flame spread index of twenty-five or less and a smoke emission rating of fifty or less using ASTM E84-23D, 2010 edition, Standard Test Method for Surface Burning Characteristics of Building Materials, or equivalent test procedures.

Source: SL 1975, ch 16, § 1; 6 SDR 93, effective July 1, 1980; 14 SDR 81, effective December 10, 1987; 22 SDR 70, effective November 19, 1995; 27 SDR 59, effective December 17, 2000; 29 SDR 81, effective December 11, 2002; transferred from § 44:04:13:25, 42 SDR 51, effective October 13, 2015; 51 SDR 53, effective November 11, 2024.

General Authority

  • SDCL 34-1-17
    Amended by HB1273 (2020) — provide certain provisions regarding the regulation of tattooing.
    Amended by HB1176 (2019) — provide for the regulation of saline tattoo removal by municipalities.
  • SDCL 34-12-13

Law Implemented