44:73:12:39Emergency

Section · Administrative Rules of South Dakota · View on sdlegislature.gov ↗

electrical service. Each facility shall have a Type 2, Essential Electrical System in accordance with the National Fire Protection Association (NFPA 99 Health Care Facilities Code, 2012 Edition). Automatic emergency lighting shall also be provided at staff work station, dining room, medication room, dietary department, room where main electrical panel is located, and boiler room. Emergency electrical service shall be provided from an automatic generator set and automatic transfer switches serving emergency panels in nursing facilities.

Source: 42 SDR 51, effective October 13, 2015.