water systems. Hot water distribution systems over 50 feet (15.24 meters) long shall recirculate to provide hot water at each fixture at all times. The hot water heating equipment shall have sufficient capacity to supply water at a minimum temperature of 140 degrees Fahrenheit (60 degrees centigrade) and amounts indicated in the following: (1) Three gallons an hour (0.0033 liters a second) for each bed; (2) Two gallons an hour (0.0020 liters a second) for each bed for dietary use; and (3) Two gallons an hour (0.0020 liters a second) per bed for laundry. Storage tanks provided shall be fabricated of noncorrosive metal or lined with noncorrosive material.